Hydrostatic test pressure calculator

In short

Under the PED 2014/68/EU and EN 13480-5, the hydrostatic test pressure is PT = max(1.25 × PS × f_test / f; 1.43 × PS). Under ASME B31.3, PT = 1.5 × P × ST / S. The gauge range is picked between 1.5 and 4 PT, as close as possible to 2 PT, from the EN 837-1 ranges.

Calculation

Example calculated with the tool’s default values.

Inputs

Maximum allowable pressure PS
10 bar
Code
PED 2014/68/EU · EN 13480-5
Height from high to low point
0 m

Results

Test pressure (high point)
14.30 bar

Worked example

Every value in this section belongs to the example, calculated with the tool’s default values.

Other results of the example

1.25 × PS × ratio
12.50 bar
1.43 × PS
14.30 bar
Gauge range (0 to …)
25 bar
PT read at … of full scale
57%
  • Indicative value: test pressure and procedure are set by the construction code and the notified body.

Step-by-step calculation

  1. Load term

    PT1 = 1.25 × PS × f_essai / f

    1.25 × 10.00 × 1.000 = 12.50 bar

  2. Minimum term

    PT2 = 1.43 × PS

    1.43 × 10.00 = 14.30 bar

  3. Test pressure

    PT = max(PT1 ; PT2)

    14.30 bar

  4. Gauge range

    1.5 PT ≤ E ≤ 4 PT, E proche de 2 PT

    21.4 ≤ E ≤ 57.2 → 0 – 25 bar

How to use it

  1. Enter the maximum allowable pressure PS, in bar.
  2. Pick the code: PED 2014/68/EU · EN 13480-5, or ASME B31.3.
  3. If the design temperature is not ambient, enter the stress ratio f_test / f_design (ST / S in B31.3); empty = 1.
  4. Enter the height from the high point to the low point of the line.
  5. Read the test pressure at the high point.

Frequently asked questions

What is the hydrostatic test pressure formula?

Under the PED 2014/68/EU (annex I § 7.4) and EN 13480-5 (§ 9.3.2), the test pressure is the larger of two values: PT1 = 1.25 × PS × f_test / f and PT2 = 1.43 × PS. The ratio f_test / f corrects for the design temperature; it is 1 for a design at ambient temperature.

What is the hydrostatic test pressure for a 10 bar line?

With PS = 10 bar under the PED, at ambient temperature: PT1 = 1.25 × 10.00 × 1.000 = 12.50 bar and PT2 = 1.43 × 10.00 = 14.30 bar. The test pressure is therefore 14.30 bar. The gauge must cover 21.4 to 57.2 bar: 0 – 25 bar range, where PT reads at 57.2 % of full scale.

What is the hydrostatic test pressure under ASME B31.3?

ASME B31.3 § 345.4.2 gives PT = 1.5 × P × ST / S, with the ST / S ratio capped at 6.5. The pressure is held for at least 10 min, then the joints are examined at no less than P (§ 345.2.2(a)). If PT would exceed yield at test temperature, B31.3 allows reducing it (§ 345.4.2(c)).

Does the line height matter?

PT applies at the high point. The low point sees the water head Δp = ρ g h / 10⁵ more, in bar: check that the low components can take it.

Limits

Indicative value: test pressure and procedure are set by the construction code and the notified body. The calculation checks neither the pipe wall thickness nor the components' strength at test pressure.

Sources

  • Directive 2014/68/UE (DESP) : Annexe I, § 7.4 (pression d’épreuve hydrostatique : max(1,25 × charge ; 1,43 × PS)) (link)
  • EN 13480-5 Tuyauteries industrielles métalliques — Inspection et contrôle : § 9.3.2 (PT = max(1,25 PS f_essai/f ; 1,43 PS))
  • Manomètre : ASME BPVC VIII-1 UG-102(b) (échelle ≈ 2 PT, entre 1,5 et 4 PT) ; échelles EN 837-1

Updated · Publisher: The Level Code